Journeyman electrician exam calculations
Journeyman exam calculations come from a short list of formulas: Ohm's law and power, single- and three-phase current, transformer current, voltage drop, continuous loads at 125%, dwelling lighting loads, box fill, motor conductor sizing, parallel resistance and conduit offsets. Learn to set each one up from memory and most calculation questions become routine.
Examples below follow the 2023 NEC. Section numbers can move between editions, so check the edition your exam uses.
Ohm's law and power
Ohm's law ties voltage (E), current (I) and resistance (R) together. Power (P) in watts is voltage times current.
E = I × RI = E ÷ R
R = E ÷ I
P = E × I
P = I² × R
P = E² ÷ R
Example: a 120-volt circuit feeds a 24-ohm resistive load. I = 120 ÷ 24 = 5 A. The load uses P = 120 × 5 = 600 W.
Try it with our free Ohm's law calculator.
Single-phase and three-phase current
For a single-phase load, current is watts divided by volts. For a balanced three-phase load, divide by volts times the square root of 3 (1.732).
Single-phase: I = P ÷ EThree-phase: I = P ÷ (E × 1.732)
Example: a 15 kW, 208-volt, three-phase heater draws I = 15,000 ÷ (208 × 1.732) = 41.6 A.
Transformer current
Transformer full-load current uses the same formula with kVA instead of watts.
Single-phase: I = kVA × 1,000 ÷ EThree-phase: I = kVA × 1,000 ÷ (E × 1.732)
Example (single-phase): a 50 kVA transformer with a 240-volt secondary: I = 50,000 ÷ 240 = 208.3 A.
Example (three-phase): a 75 kVA, 480 to 208Y/120-volt transformer. Primary: 75,000 ÷ (480 × 1.732) = 90.2 A. Secondary: 75,000 ÷ (208 × 1.732) = 208.2 A.
Voltage drop
Voltage drop uses the conductor's resistivity constant (K), the current, the one-way length in feet and the conductor's area in circular mils (CM), from NEC Chapter 9, Table 8.
Single-phase: VD = 2 × K × I × L ÷ CMThree-phase: VD = 1.732 × K × I × L ÷ CM
Use K = 12.9 for copper and K = 21.2 for aluminum unless the question gives you a value. The NEC recommends, in informational notes, keeping branch-circuit voltage drop to 3% and the combined feeder and branch circuit to 5%.
Example (single-phase): 120 volts, 20 A, 100 ft one way, 12 AWG copper (6,530 CM). VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V, which is 6.6% of 120 V. Too much. 10 AWG gives 4.1%, still over 3%. 8 AWG (16,510 CM) gives 3.1 V, or 2.6%.
Example (three-phase): 208 volts, 40 A, 150 ft, 8 AWG copper. VD = 1.732 × 12.9 × 40 × 150 ÷ 16,510 = 8.1 V, or 3.9%. Upsizing to 6 AWG (26,240 CM) gives 5.1 V, or 2.5%.
Check your own numbers with our free voltage drop calculator.
| Copper size | Area (circular mils) |
|---|---|
| 14 AWG | 4,110 |
| 12 AWG | 6,530 |
| 10 AWG | 10,380 |
| 8 AWG | 16,510 |
| 6 AWG | 26,240 |
| 4 AWG | 41,740 |
| 3 AWG | 52,620 |
| 2 AWG | 66,360 |
| 1 AWG | 83,690 |
| 1/0 AWG | 105,600 |
Continuous loads at 125%
A continuous load runs for three hours or more. Overcurrent devices and conductors for continuous loads are sized at 125% of the continuous load plus 100% of the noncontinuous load (210.19(A)(1), 210.20(A), 215.2(A)(1) and 215.3).
Minimum rating = (continuous load × 1.25) + noncontinuous loadExample: a branch circuit supplies 16 A of continuous lighting. 16 × 1.25 = 20 A minimum overcurrent device.
Dwelling general lighting load
For dwelling units, the general lighting load is 3 volt-amperes per square foot of livable floor area (220.41). Open porches, garages and unused spaces not adaptable for future use are left out.
Example: a 2,400 sq ft house: 2,400 × 3 = 7,200 VA general lighting load, before demand factors.
Box fill
Each conductor and item in a box uses a volume allowance from Table 314.16(B)(1), based on conductor size. Count them using 314.16(B), then multiply.
| Conductor size | Volume per conductor |
|---|---|
| 14 AWG | 2.00 in³ |
| 12 AWG | 2.25 in³ |
| 10 AWG | 2.50 in³ |
| 8 AWG | 3.00 in³ |
| 6 AWG | 5.00 in³ |
How to count:
- Each conductor that enters and ends or splices in the box: 1.
- Internal cable clamps, all together: 1, based on the largest conductor.
- Each device yoke (receptacle or switch): 2, based on the largest conductor connected to it.
- Equipment grounding conductors: 1 for up to four, plus 1/4 for each one beyond four.
Example: a box has four 12 AWG insulated conductors, two 12 AWG equipment grounding conductors, internal clamps and one receptacle. Count: 4 + 1 + 1 + 2 = 8. Volume: 8 × 2.25 = 18.0 in³ minimum.
Motor branch-circuit conductors
Size motor conductors from the full-load current in the NEC motor tables (Tables 430.247 to 430.250), not the nameplate (430.6(A)(1)). Branch-circuit conductors for a single motor must be rated at least 125% of that full-load current (430.22).
Example: a three-phase motor has a table full-load current of 28 A. 28 × 1.25 = 35 A minimum conductor ampacity.
Parallel resistance
1 ÷ RT = 1 ÷ R1 + 1 ÷ R2 + 1 ÷ R3 ...Example: 12, 12 and 6 ohms in parallel: 1 ÷ (1/12 + 1/12 + 1/6) = 3 ohms. For two resistors, the shortcut is (R1 × R2) ÷ (R1 + R2).
Conduit offsets
Distance between bends equals the offset depth times the multiplier for the bend angle. Shrink is how much the offset shortens the run.
| Bend angle | Multiplier | Shrink per inch of offset |
|---|---|---|
| 10° | 6.0 | 1/16 in |
| 22.5° | 2.6 | 3/16 in |
| 30° | 2.0 | 1/4 in |
| 45° | 1.414 | 3/8 in |
| 60° | 1.155 | 1/2 in |
Example: a 6 in offset with 30° bends: 6 × 2 = 12 in between bends, and 6 × 1/4 = 1.5 in of shrink.
Frequently asked questions
What percentage of the journeyman exam is calculations?
It varies by exam. Some states mix calculations into one test; others, like Texas, give calculations their own part. Expect calculations to be a significant share either way, and expect them to be where most people lose points.
What K value should I use for voltage drop?
Use the value the question gives. If none is given, 12.9 for copper and 21.2 for aluminum are the standard values in most exam prep and reference books.
Do I need to memorize formulas for the journeyman exam?
You should know the core formulas by heart. Exams usually allow the NEC and a basic calculator but not your own notes, and the NEC doesn't print formulas like voltage drop or three-phase current in the rules you'll be looking up.
What calculator can I use on the journeyman exam?
Most testing vendors allow a basic, non-programmable calculator. Some provide one. Your candidate bulletin lists what's allowed.