Voltage drop calculator

Short answer

Enter the circuit voltage, load current, one-way length and conductor size. The calculator gives the voltage drop, the percent of supply voltage and, if the drop is over 3%, the smallest larger wire size that brings it under.

Voltage drop
7.9 V6.6%

Over 3%. 8 AWG brings it to 2.6%.

K = 12.9 for copper, 21.2 for aluminum. Conductor areas from NEC Chapter 9, Table 8.

How voltage drop is calculated

This calculator uses the standard formula found in exam prep and NEC references:

Single-phase: VD = 2 × K × I × L ÷ CM
Three-phase: VD = 1.732 × K × I × L ÷ CM
  • K is the resistivity constant: 12.9 for copper, 21.2 for aluminum.
  • I is the load current in amps.
  • L is the one-way length of the circuit in feet.
  • CM is the conductor area in circular mils, from NEC Chapter 9, Table 8.

Percent voltage drop is the drop divided by the supply voltage, times 100.

Worked example

A 120-volt, 20 A load is 100 ft from the panel on 12 AWG copper.

VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V, which is 6.6% of 120 V. Moving up to 8 AWG (16,510 CM) cuts it to 3.1 V, or 2.6%.

How much voltage drop is allowed?

The NEC doesn't set a hard limit for most circuits. Informational notes recommend sizing branch circuits for no more than 3% voltage drop, and feeders plus branch circuits together for no more than 5%. Some articles, such as those for fire pumps and sensitive electronic equipment, do set mandatory limits. Exam questions usually ask you to stay at or under 3% for a branch circuit.

Frequently asked questions

Is the length one way or round trip?

One way. The 2 in the single-phase formula already accounts for the current going out and back.

Why does three-phase use 1.732 instead of 2?

In a balanced three-phase circuit the return current is shared between the phases, so the multiplier is the square root of 3 (1.732) rather than 2.

Does this calculator account for power factor or conductor temperature?

No. It uses the common exam method with fixed K values, which assumes a resistive load. For real installations with long runs or large motors, use the conductor resistance and reactance values in NEC Chapter 9, Table 9.